Category: Converter Manual Article
-

MCB faults
This article concerns the Schneider NSX 100 circuit breaker used in Sirius. In Sirius we have only connected the SD contact which indicates ANY kind of trip – even one coming from the undervoltage coil. This is why we always have the fault MCB. MCB origin Cause State card DIM Fault Label SKMCB pin15 to
-

Kill a linux script
When running an automatic parameter identification script (using FGCRun+ menus) the script may not be properly terminated and the converter keeps turning on and off by itself. To force stop these scripts that run on the cs-ccr-teepc2 linux machine on technical network you need to connect to cs-ccr-teepc2 using a terminal (such as putty) and
-

REF.CYC.STATUS gives PRE_FUNC_WRN
The pre-function error (in seconds) is given using the G REF.CYC.PRE_FUNC_ERR(#usr). This value returns the difference between a theoretical pre-function time and the actual pre-function the fgc managed to play in the time available. The theoretical value is calculated by adding the calculated times of ramping up, the duration of the MAGCYCLE plateau (REF.DEFAULTS.PLATEAU_DUR[0]), any
-

Current loop properties
This property contains the period for the operational current regulation algorithm. With 10 it means a sampling rate of 1kHz which is normally fine for our application and that Auxpole 1 and 2 could reach a value of 100Hz. This property contains the pure delay in iterations between the calculation of the actuation by the
-

Tunning loops with low inductive load
When the circuit inductance is very low (1.4mH in this example). If identification was made with PowerSpy to calculate the differential inductance Ld = (Vmag- rmag x Imag)/(di_dt), with a very low inductance the accuracy of the calculation for Ld is a function of how accurate the measurement of rmag was made in DC (at