Test facilities

Magnet Test Lab – Building 311-R-001 (Meyrin)

NameTypeVoltage (V)Electric departureInstallation Guide
DCPeak
RPADA.311.COMET_2P.1COMET 2p500500120ERD102*83.edms
RPADA.311.COMET_2P.2COMET 2p500500120ERD103*83.edms
RPADG.311.APOLO_2P.1APOLO 2p400900450ERD112*83.edms
RPMC.311.TRANSTECHNIK.1Transtechnik60060040
RPMC.311.TRANSTECHNIK.2Transtechnik60060040
RPMC.311.TRANSTECHNIK.3Transtechnik60060040
RPAGE.311.COMET_4P.1COMET 2x 2p10001000120ERD113*83.edms

Magnet Test Lab – Building 867-R-H29 (Prevessin)

NameTypeVoltage (V)Electric departureInstallation Guide
DCPeak
RPAFB.867.SIRIUS_4P.1SIRIUS 4P8001800450400V/125A 3phEDMS 1870848
S250.B1S250B25025040400V
S250.B2S250B25025040400V
HOLEC
SEPTUMR40-8672400060400V
HAZEMHAZEM6500220400V
RPHFA.867.MAGTEST.1RPHFA80008400V
NR21-046R21-MIB1000300400V
NR22-074R22-BBC1500250400V
NR71-001R71640060400V

EPC Group Test Lab – Bat. 287-R-003

NameTypeVoltage (V)Departure ElectricInstallation Guide
DCPeak
RPAEJ.A7.SIRIUS.S.1Sirius S400900450400V/63A 3ph

RPAEK.A7.SIRIUS.2P.1

Sirius 2P400900450400V/63A 3ph
RPAFB.A7.SIRIUS.4P.1Sirius 4P8001800450

Operation Guide

2.1 Start-up and diagnostics

The power converters provided by EPC require the following connections:

  • Electrical departure according to requirements (see table above) and protective ground (provided by EN/EL)
  • Electrical connection to load (provided by the user)
  • FGC Ether network connection for remote control (provided by EPC-CC)
  • External interlock (typically thermal interlock switch from load) (provided by the user)

NOTE: The first time a power converter is commissioned, this should be done by a specialist

2.2 Supplying a DC current to the laod

The power converter is controlled remotely from a desktop or laptop through the CERN technical network. From the technical network the user must access FGCRun+ provided by EPC. A login is required with your CERN account which needs to be configured for accessing this service (contact converter-controls@cern.ch).

Once you access the software you can add devices (converters) to your control list by typing their name which can be found on the dongle label. Note: the commands you type are sent to ALL open devices unless you select the one you wish to control. To only keep one device in your device list, select it by clicking on it and press CTRL-T.

You can send a command to a device by typing in the bottom text field of the window and pressing enter. Two types of commands are available; the "S" or SET and the "G" or GET commands.

For example S PC OF turns off the power converter. Here is how to turn on a power converter and apply a DC current to the load.

#the following command performs a reset in case of faults (for example an open door or fast stop button will lock the converter into FAULT condition).
S PC OF

#turn on the converter to Stand-by mode.It can take up to 50seconds to start the power converter
S PC SB

#change mode to IDLE (waiting a command for the current)
S PC IL

#set the current to a DC value of 100A immediately after the command is sent
S REF NOW,100

#turn of the power converter (first to STAND BY and then to OFF)
S PC SB
S PC OF

2.3 Supplying an cycling current to the load